Article 503
Class III Locations
Part I. General
503.1 Scope. Article 503 covers the requirements for electri‐ cal and electronic equipment and wiring for all voltages in Class III, Division 1 and 2 locations where fire or explosion hazards may exist due to ignitible fibers/flyings.
- General. Equipment installed in Class III locations shall be able to function at full rating without developing surface temperatures high enough to cause excessive dehydration or gradual carbonization of accumulated fibers/flyings. Organic material that is carbonized or excessively dry is highly suscepti‐ ble to spontaneous ignition. The maximum surface tempera‐ tures under operating conditions shall not exceed 165°C (329°F) for equipment that is not subject to overloading, and 120°C (248°F) for equipment (such as motors or power trans‐ formers) that may be overloaded. In a Class III, Division 1 loca‐ tion, the operating temperature shall be the temperature of the equipment when blanketed with the maximum amount of dust (simulating fibers/flyings) that can accumulate on the equipment.Informational Note: For electric trucks, see NFPA 505-2013, Fire Safety Standard for Powered Industrial Trucks Including Type Designa‐ tions, Areas of Use, Conversions, Maintenance, and Operation.
- Zone Equipment. Equipment listed and marked in accordance with 506.9(C)(2) for Zone 20 locations and with a temperature class of not greater than T120°C (for equipment that may be overloaded) or not greater than T165°C (for equipment not subject to overloading) shall be permitted in Class III, Division 1 locations.
Equipment listed and marked in accordance with 506.9(C)
(2) for Zone 20, 21, or 22 locations and with a temperature
class of not greater than T120°C (for equipment that may be overloaded) or not greater than T165°C (for equipment not subject to overloading) shall be permitted in Class III, Divi‐ sion 2 locations.
Part II. Wiring
503.10 Wiring Methods. Wiring methods shall comply with 503.10(A) or (B).
- Class III, Division 1.
- General. In Class III, Division 1 locations, the wiring method shall be in accordance with (1) through (5):
- Rigid metal conduit, Type PVC conduit, Type RTRC conduit, intermediate metal conduit, electrical metallic tubing, dusttight wireways, or Type MC or MI cable with listed termination fittings.
- Type PLTC and Type PLTC-ER cable in accordance with the provisions of Article 725, including installation in cable tray systems. The cable shall be terminated with listed fittings.
- Type ITC and Type ITC-ER cable as permitted in 727.4 and terminated with listed fittings.
- Type MC, MI, MV, TC, or TC-ER cable installed in ladder, ventilated trough, or ventilated channel cable trays in a single layer, with a space not less than the larger cable diameter between the two adjacent cables, shall be the wiring method employed. The cable shall be terminated with listed fittings.Exception to (4): Type MC cable listed for use in Class II, Division 1 locations shall be permitted to be installed without the spacings required by 503.10(A)(1)(4).
- Cablebus.
- Boxes and Fittings. All boxes and fittings shall be dust‐ tight.
- Flexible Connections. Where necessary to employ flexible connections, one or more of the following shall be permitted:
- Dusttight flexible connectors
- Liquidtight flexible metal conduit with listed fittings
- Liquidtight flexible nonmetallic conduit with listed fittings
- Interlocked armor Type MC cable having an overall jacket of suitable polymeric material and installed with listed dusttight termination fittings
- Flexible cord in compliance with 503.140Informational Note: See 503.30(B) for grounding requirements where flexible conduit is used.
- For elevator use, an identified elevator cable of Type EO, ETP, or ETT, shown under the “use” column in Table
Informational Note: Simple apparatus is defined in 504.2.Separate nonincendive field wiring circuits shall be installed in accordance with one of the following:- In separate cables
- In multiconductor cables where the conductors of each circuit are within a grounded metal shield
- In multiconductor cables where the conductors of each circuit have insulation with a minimum thickness of 0.25 mm (0.01 in.)
- General. In Class III, Division 1 locations, the wiring method shall be in accordance with (1) through (5):
- Class III, Division 2. In Class III, Division 2 locations, the wiring method shall comply with 503.10(A).
Exception: In sections, compartments, or areas used solely for storage and containing no machinery, open wiring on insulators shall be permitted where installed in accordance with Article 398, but only on condition that protection as required by 398.15(C) be provided where conductors are not run in roof spaces and are well out of reach of sour‐ ces of physical damage.
503.25 Uninsulated Exposed Parts, Class III, Divisions 1 and 2. There shall be no uninsulated exposed parts, such as electrical conductors, buses, terminals, or components, that operate at more than 30 volts (15 volts in wet locations). These parts shall additionally be protected by a protection technique according to 500.7(E), (F), or (G) that is suitable for the location.
Exception: As provided in 503.155.
503.30 Grounding and Bonding — Class III, Divisions 1 and 2. Regardless of the voltage of the electrical system, wiring and equipment in Class III, Division 1 and 2 locations shall be
Part III. Equipment
503.100 Transformers and Capacitors — Class III, Divisions 1 and 2. Transformers and capacitors shall comply with 502.100(B).
503.115 Switches, Circuit Breakers, Motor Controllers, and Fuses — Class III, Divisions 1 and 2. Switches, circuit break‐ ers, motor controllers, and fuses, including pushbuttons, relays, and similar devices, shall be provided with dusttight enclosures.
503.120 Control Transformers and Resistors — Class III, Divi‐ sions 1 and 2. Transformers, impedance coils, and resistors used as, or in conjunction with, control equipment for motors, generators, and appliances shall be provided with dusttight enclosures complying with the temperature limitations in 503.5.
503.125 Motors and Generators — Class III, Divisions 1 and 2. In Class III, Divisions 1 and 2 locations, motors, generators, and other rotating machinery shall be totally enclosed nonven‐ tilated, totally enclosed pipe ventilated, or totally enclosed fan cooled.
Exception: In locations where, in the judgment of the authority having jurisdiction, only moderate accumulations of lint or flyings are likely to collect on, in, or in the vicinity of a rotating electrical machine and where such machine is readily accessible for routine cleaning and main‐ tenance, one of the following shall be permitted:
- Self-cleaning textile motors of the squirrel-cage type
- Standard open-type machines without sliding contacts, centrifu‐ gal or other types of switching mechanisms, including motor over‐grounded as specified in Article 250 and with the following additional requirements in 503.30(A) and (B).
- Bonding. The locknut-bushing and double-locknut types
load devices
Standard open-type machines having such contacts, switching mechanisms, or resistance devices enclosed within tight housings without ventilating or other openings
of contacts shall not be depended on for bonding purposes, but bonding jumpers with proper fittings or other approved means of bonding shall be used. Such means of bonding shall apply to all intervening raceways, fittings, boxes, enclosures, and so forth, between Class III locations and the point of grounding for service equipment or point of grounding of a separately derived system.
Exception: The specific bonding means shall only be required to the nearest point where the grounded circuit conductor and the grounding electrode conductor are connected together on the line side of the build‐ ing or structure disconnecting means as specified in 250.32(B) if the branch-circuit overcurrent protection is located on the load side of the disconnecting means.
(B) Types of Equipment Bonding Conductors. Liquidtight flexible metal conduit shall include an equipment bonding jumper of the wire type in compliance with 250.102.
Exception: In Class III, Division 1 and 2 locations, the bonding jumper shall be permitted to be deleted where all of the following condi‐ tions are met:
- Listed liquidtight flexible metal conduit 1.8 m (6 ft) or less in length, with fittings listed for grounding, is used.
- Overcurrent protection in the circuit is limited to 10 amperes or less.
- The load is not a power utilization load.
503.128 Ventilating Piping — Class III, Divisions 1 and 2. Ventilating pipes for motors, generators, or other rotating elec‐ trical machinery, or for enclosures for electric equipment, shall be of metal not less than 0.53 mm (0.021 in.) in thickness, or of equally substantial noncombustible material, and shall comply with the following:
- Lead directly to a source of clean air outside of buildings
- Be screened at the outer ends to prevent the entrance of small animals or birds
- Be protected against physical damage and against rusting or other corrosive influences
Ventilating pipes shall be sufficiently tight, including their connections, to prevent the entrance of appreciable quantities of fibers/flyings into the ventilated equipment or enclosure and to prevent the escape of sparks, flame, or burning material that might ignite accumulations of fibers/flyings or combusti‐ ble material in the vicinity. For metal pipes, lock seams and riveted or welded joints shall be permitted; and tight-fitting slip joints shall be permitted where some flexibility is necessary, as at connections to motors.
503.130 Luminaires — Class III, Divisions 1 and 2.
- Fixed Lighting. Luminaires for fixed lighting shall provide enclosures for lamps and lampholders that are designed to minimize entrance of fibers/flyings and to prevent the escape of sparks, burning material, or hot metal. Each luminaire shall be clearly marked to show the maximum wattage of the lamps that shall be permitted without exceeding
an exposed surface temperature of 165°C (329°F) under normal conditions of use. - Physical Damage. A luminaire that may be exposed to physical damage shall be protected by a suitable guard.
- Pendant Luminaires. Pendant luminaires shall be suspen‐ ded by stems of threaded rigid metal conduit, threaded inter‐ mediate metal conduit, threaded metal tubing of equivalent thickness, or by chains with approved fittings. For stems longer than 300 mm (12 in.), permanent and effective bracing against lateral displacement shall be provided at a level not more than 300 mm (12 in.) above the lower end of the stem, or flexibility in the form of an identified fitting or a flexible connector shall be provided not more than 300 mm (12 in.) from the point of attachment to the supporting box or fitting.
- Portable Lighting Equipment. Portable lighting equip‐ ment shall be equipped with handles and protected with substantial guards. Lampholders shall be of the unswitched type with no provision for receiving attachment plugs. There shall be no exposed current-carrying metal parts, and all exposed non–current-carrying metal parts shall be grounded. In all other respects, portable lighting equipment shall comply with 503.130(A).
503.135 Utilization Equipment — Class III, Divisions 1 and 2.
- Heaters. Electrically heated utilization equipment shall be identified for Class III locations.
- Motors. Motors of motor-driven utilization equipment shall comply with 503.125.
- Switches, Circuit Breakers, Motor Controllers, and Fuses. Switches, circuit breakers, motor controllers, and fuses shall comply with 503.115.
503.140 Flexible Cords — Class III, Divisions 1 and 2. Flexi‐ ble cords shall comply with the following:
- Be of a type listed for extra-hard usage
- Contain, in addition to the conductors of the circuit, an equipment grounding conductor complying with 400.23
- Be supported by clamps or other suitable means in such a manner that there will be no tension on the terminal connections
- Be terminated with a listed dusttight cord connector.
503.145 Receptacles and Attachment Plugs — Class III, Divi‐ sions 1 and 2. Receptacles and attachment plugs shall be of the grounding type, shall be designed so as to minimize the accumulation or the entry of fibers/flyings, and shall prevent the escape of sparks or molten particles.
Exception: In locations where, in the judgment of the authority having jurisdiction, only moderate accumulations of lint or flyings are likely to collect in the vicinity of a receptacle, and where such receptacle is readily accessible for routine cleaning, general-purpose grounding-type recepta‐ cles mounted so as to minimize the entry of fibers/flyings shall be permitted.
503.150 Signaling, Alarm, Remote-Control, and Local Loud‐ speaker Intercommunications Systems — Class III, Divisions 1 and 2. Signaling, alarm, remote-control, and local loud‐ speaker intercommunications systems shall comply with the requirements of Article 503 regarding wiring methods, switches, transformers, resistors, motors, luminaires, and rela‐ ted components.
503.155 Electric Cranes, Hoists, and Similar Equipment — Class III, Divisions 1 and 2. Where installed for operation over combustible fibers or accumulations of flyings, traveling cranes and hoists for material handling, traveling cleaners for textile machinery, and similar equipment shall comply with 503.155(A) through (D).
- Power Supply. The power supply to contact conductors shall be electrically isolated from all other systems, ungroun‐ ded, and shall be equipped with an acceptable ground detector that gives an alarm and automatically de-energizes the contact conductors in case of a fault to ground or gives a visual and audible alarm as long as power is supplied to the contact conductors and the ground fault remains.
- Contact Conductors. Contact conductors shall be located or guarded so as to be inaccessible to other than authorized persons and shall be protected against accidental contact with foreign objects.
- Current Collectors. Current collectors shall be arranged or guarded so as to confine normal sparking and prevent escape of sparks or hot particles. To reduce sparking, two or more separate surfaces of contact shall be provided for each contact conductor. Reliable means shall be provided to keep contact conductors and current collectors free of accumula‐ tions of lint or flyings.
- Control Equipment. Control equipment shall comply with 503.115 and 503.120.
503.160 Storage Battery Charging Equipment — Class III, Divisions 1 and 2. Storage battery charging equipment shall be located in separate rooms built or lined with substantial noncombustible materials. The rooms shall be constructed to prevent the entrance of ignitible amounts of flyings or lint and shall be well ventilated