Article 402

Fixture Wires

  1. Scope. This article covers general requirements and construction specifications for fixture wires.
  2. Other Articles. Fixture wires shall comply with this arti‐ cle and also with the applicable provisions of other articles of this Code.Informational Note: For application in luminaires, see Article 410.
  3. Types. Fixture wires shall be of a type listed in Table 402.3, and they shall comply with all requirements of that table. The fixture wires listed in Table 402.3 are all suitable for service at 600 volts, nominal, unless otherwise specified.

Informational Note: Thermoplastic insulation may stiffen at temperatures lower than −10°C (+14°F). Thermoplastic insula‐ tion may also be deformed at normal temperatures where subjected to pressure, such as at points of support.

402.3 ARTICLE 402 — FIXTURE WIRES

Table 402.3 Fixture Wires


Name

Type Letter

Insulation

AWG
Thickness of Insulation
Outer Covering

Maximum Operating Temperature

Application Provisions

mm

mils
Heat-resistant rubber- covered fixture wire — flexible strandingFFH-2Heat-resistant rubberCross-linked synthetic polymer18–16
18–16
0.76
0.76
30
30
Nonmetallic covering75°C (167°F)Fixture wiring
ECTFE — solid or 7-strandHFEthylene chloro-trifluoroethylene18–140.3815None150°C (302°F)Fixture wiring
ECTFE — flexible strandingHFFEthylene chlorotrifluo- roethylene18–140.3815None150°C (302°F)Fixture wiring
Tape insulated fixture wire — solid or 7-strandKF-1
KF-2
Aromatic polyimide tapeAromatic polyimide tape18–10
18–10
0.14
0.21
5.5
8.4
None
None
200°C (392°F)
200°C (392°F)
Fixture wiring— limited to 300 voltsFixture wiring
Tape insulated fixture wire — flexible strandingKFF-1
KFF-2
Aromatic polyimide tapeAromatic polyimide tape18–10
18–10
0.14
0.21
5.5
8.4
None
None
200°C (392°F)
200°C (392°F)
Fixture wiring— limited to 300 voltsFixture wiring
Perfluoro-alkoxy — solid or 7-strand (nickel or nickel-coated copper)PAFPerfluoro- alkoxy18–140.5120None250°C
(482°F)
Fixture wiring (nickel or nickel-coated copper)
Perfluoro-alkoxy — flexible strandingPAFFPerfluoro- alkoxy18–140.5120None150°C (302°F)Fixture wiring
Fluorinated ethylene propylene fixture wire— solid or 7-strandPFFluorinated ethylene propylene18–140.5120None200°C (392°F)Fixture wiring
Fluorinated ethylene propylene fixture wire— flexible strandingPFFFluorinated ethylene propylene18–140.5120None150°C (302°F)Fixture wiring
Fluorinated ethylene propylene fixture wire— solid or 7-strandPGFFluorinated ethylene propylene18–140.3614Glass braid200°C (392°F)Fixture wiring
Fluorinated ethylene propylene fixture wire— flexible strandingPGFFFluorinated ethylene propylene18–140.3614Glass braid150°C (302°F)Fixture wiring
Extruded polytetrafluoroethylene— solid or 7-strand (nickel or nickel-coated copper)PTFExtruded polytetrafluo- roethylene18–140.5120None250°C (482°F)Fixture wiring (nickel or nickel-coated copper)
Extruded polytetrafluoroethylene— flexible stranding 26-36 (AWG silver or nickel-coated copper)PTFFExtruded polytetrafluo- roethylene18–140.5120None150°C (302°F)Fixture wiring (silver or nickel-coated copper)

(continues)

Table 402.3 Continued


Name

Type Letter

Insulation

AWG
Thickness of Insulation
Outer Covering

Maximum Operating Temperature

Application Provisions

mm

mils
Heat-resistant rubber- covered fixture wire — solid or 7-strandRFH-1Heat-resistant rubber180.3815Nonmetallic covering75°C (167°F)Fixture wiring— limited to 300 volts
RFH-2Heat-resistant rubber Cross-linked synthetic polymer18–160.7630None or non- metallic covering75°C (167°F)Fixture wiring
Heat-resistant cross-linked synthetic polymer- insulated fixture wire— solid or 7-strandRFHH-2* RFHH-3*Cross-linked synthetic polymer18–1618–160.761.143045None or non- metallic covering90°C (194°F)Fixture wiring
Silicone insulated fixture wire — solid or 7-strandSF-1Siliconerubber180.3815Nonmetallic covering200°C (392°F)Fixture wiring— limited to 300 volts
SF-2Siliconerubber18–12100.761.143045Nonmetallic covering200°C (392°F)Fixture wiring
Silicone insulated fixture wire — flexible strandingSFF-1Siliconerubber180.3815Nonmetallic covering150°C (302°F)Fixture wiring— limited to 300 volts
SFF-2Siliconerubber18–12100.761.143045Nonmetallic covering150°C (302°F)Fixture wiring
Thermoplastic covered fixture wire — solid or 7-strandTF*Thermoplastic18–160.7630None60°C (140°F)Fixture wiring
Thermoplastic covered fixture wire — flexible strandingTFF*Thermoplastic18–160.7630None60°C (140°F)Fixture wiring
Heat-resistant thermoplastic covered fixture wire — solid or 7-strandTFN*Thermoplastic18–160.3815Nylon-jacket- ed orequivalent90°C (194°F)Fixture wiring
Heat-resistant thermoplastic covered fixture wire — flexible strandedTFFN*Thermoplastic18–160.3815Nylon-jacket- ed orequivalent90°C (194°F)Fixture wiring
Cross-linked polyolefin insulated fixture wire— solid or 7-strandXF*Cross-linked polyolefin18–1412-100.761.143045None150°C (302°F)Fixture wiring— limited to 300 volts
Cross-linked polyolefin insulated fixture wire— flexible strandedXFF*Cross-linked polyolefin18–1412–100.761.143045None150°C (302°F)Fixture wiring— limited to 300 volts
Modified ETFE — solid or 7-strandZFModified ethylene tetrafluoro- ethylene18–140.3815None150°C (302°F)Fixture wiring
Flexible strandingZFFModified ethylene tetrafluoro- ethylene18–140.3815None150°C (302°F)Fixture wiring
High temp. modified ETFE— solid or 7- strandZHFModified ethylene tetrafluoro- ethylene18–140.3815None200°C (392°F)Fixture wiring

*Insulations and outer coverings that meet the requirements of flame retardant, limited smoke, and are so listed, shall be permitted to be marked for limited smoke after the Code type designation.

  1. Allowable Ampacities for Fixture Wires. The allowable ampacity of fixture wire shall be as specified in Table 402.5.No conductor shall be used under such conditions that its operating temperature exceeds the temperature specified in Table 402.3 for the type of insulation involved.Informational Note: See 310.15(A)(3) for temperature limita‐ tion of conductors.
  2. Minimum Size. Fixture wires shall not be smaller than 18 AWG.
  3. Number of Conductors in Conduit or Tubing. The number of fixture wires permitted in a single conduit or tubing shall not exceed the percentage fill specified in Table 1, Chap‐ ter 9.
  4. Grounded Conductor Identification. Fixture wires that are intended to be used as grounded conductors shall be iden‐ tified by one or more continuous white stripes on other than green insulation or by the means described in 400.22(A) through (E).
  5. Marking.
    1. Method of Marking. Thermoplastic insulated fixture wire shall be durably marked on the surface at intervals not exceed‐ ing 610 mm (24 in.). All other fixture wire shall be marked by means of a printed tag attached to the coil, reel, or carton.
    2. Optional Marking. Fixture wire types listed in Table 402.3 shall be permitted to be surface marked to indicate special characteristics of the cable materials. These markings include, but are not limited to, markings for limited smoke, sunlight resistance, and so forth.
  6. Uses Permitted. Fixture wires shall be permitted

(1) for installation in luminaires and in similar equipment where enclosed or protected and not subject to bending or twisting in use, or (2) for connecting luminaires to the branch- circuit conductors supplying the luminaires.

402.12 Uses Not Permitted. Fixture wires shall not be used as branch-circuit conductors except as permitted elsewhere in this Code.

402.14 Overcurrent Protection. Overcurrent protection for fixture wires shall be as specified in 240.5.

Size (AWG)Allowable Ampacity
186
168
1417
1223
1028

Table 402.5 Allowable Ampacity for Fixture Wires

Sidebar