Article 374
Cellular Metal Floor Raceways
Part I. General
- Scope. This article covers the use and installation requirements for cellular metal floor raceways.
- Definitions.
Cellular Metal Floor Raceway. The hollow spaces of cellular metal floors, together with suitable fittings, that may be approved as enclosed channel for electrical conductors.
Cell. A single enclosed tubular space in a cellular metal floor member, the axis of the cell being parallel to the axis of the metal floor member.
Header. A transverse raceway for electrical conductors, provid‐ ing access to predetermined cells of a cellular metal floor, thereby permitting the installation of electrical conductors from a distribution center to the cells.
Part II. Installation
374.12 Uses Not Permitted. Conductors shall not be installed in cellular metal floor raceways as follows:
- Where subject to corrosive vapor
- In any hazardous (classified) location, except as permit‐ ted by other articles in this Code
- In commercial garages, other than for supplying ceiling outlets or extensions to the area below the floor but not above
Informational Note: See 300.8 for installation of conductors with other systems.
374.18 Cellular Metal Floor Raceways Installations. Installa‐ tion of cellular metal floor raceways shall comply with 374.18(A) through 374.18(D).
- Connection to Cabinets and Extensions from Cells. Connections between raceways and distribution centers and wall outlets shall be made by means of liquidtight flexible metal conduit, flexible metal conduit where not installed in concrete, rigid metal conduit, intermediate metal conduit, electrical metallic tubing, or approved fittings. Where there are provi‐ sions for the termination of an equipment grounding conduc‐ tor, rigid polyvinyl chloride conduit, reinforced thermosetting resin conduit, electrical nonmetallic tubing, or liquidtight flexi‐ ble nonmetallic conduit shall be permitted. Where installed in concrete, liquidtight flexible metal conduit and liquidtight flexible nonmetallic conduit shall be listed and marked for direct burial.
- Junction Boxes. Junction boxes shall be leveled to the floor grade and sealed against the free entrance of water or concrete. Junction boxes used with these raceways shall be of metal and shall be electrically continuous with the raceway.
- Inserts. Inserts shall be leveled to the floor grade and sealed against the entrance of concrete. Inserts shall be of metal and shall be electrically continuous with the raceway. In cutting through the cell wall and setting inserts, chips and other dirt shall not be allowed to remain in the raceway, and374.18 ARTICLE 376 — METAL WIREWAYS
tools shall be used that are designed to prevent the tool from entering the cell and damaging the conductors. - Markers. A suitable number of markers shall be installed for locating cells in the future.
374.20 Size of Conductors. No conductor larger than 1/0 AWG shall be installed, except by special permission.
- Maximum Number of Conductors in Raceway. The combined cross-sectional area of all conductors or cables shall not exceed 40 percent of the interior cross-sectional area of the cell or header.
- Ampacity of Conductors. The ampacity adjustment factors in 310.15(B)(3) shall apply to conductors installed in cellular metal floor raceways.
374.56 Splices and Taps. Splices and taps shall be made only in header access units or junction boxes.
For the purposes of this section, so-called loop wiring (continuous unbroken conductor connecting the individual outlets) shall not be considered to be a splice or tap.
374.58 Discontinued Outlets. When an outlet is abandoned, discontinued, or removed, the sections of circuit conductors supplying the outlet shall be removed from the raceway. No splices or reinsulated conductors, such as would be the case with abandoned outlets on loop wiring, shall be allowed in raceways.
Part III. Construction Specifications
374.100 General. Cellular metal floor raceways shall be constructed so that adequate electrical and mechanical continuity of the complete system will be secured. They shall provide a complete enclosure for the conductors. The interior surfaces shall be free from burrs and sharp edges, and surfaces over which conductors are drawn shall be smooth. Suitable bushings or fittings having smooth rounded edges shall be provided where conductors pass.